Input
Phases | 2 3 |
Nominal input voltage Ui nom | (2 / 3) x AC 400 … 500 V |
Input voltage range | (2 / 3) x AC 340 … 550 V; DC 480 … 780 V |
Nominal mains frequency range | 50 … 60 Hz; 0 Hz |
Input current Ii | ≤ 3 x 1.1 A (340 VAC; 20 ADC) |
Discharge current | ≤ 1 mA |
Inrush current | ≤ 30 A |
Power factor correction (PFC) | Passive (changeable via software/display) |
Mains failure hold-up time | ≥ 13 ms (3 x 400 VAC) |
Nominal output voltage Uo nom | DC 24 V (SELV) |
Output voltage range | DC 22.8 … 28.8 V (adjustable) |
Factory preset | DC 24 V |
Nominal output current Io nom | 20 A (24 VDC) |
Nominal output power | 480 W |
Adjustment accuracy | ≤ 1 % |
Residual ripple | ≤ 70 mV (peak-to-peak) |
Current limitation | 1.1 x Io nom typ. |
Overload behavior | Adjustable (constant current/fuse mode) |
PowerBoost | DC 40 A (4 s); DC 30 A (16 s) |
TopBoost | DC 80 A (50 ms) |
Signaling | 1 x LED DC OK (green) 1 x LED warning (yellow) 1 x LED error (red) LCD 4 x signal output (24 VDC, max. 25 mA) 1 x RS-232 interface |
Operation status indicator | LED green (DC OK) LED yellow (warning) LED red (error) |
Communication | RS-232 serial interface |
Power loss Pv | ≤ 8.3 W (no load); ≤ 34.1 W (nominal load) |
Efficiency (typ.) | 92.9 % |
Internal fuse | 3 x T 2.5 A / 440 VAC |
External fuse (required) | an external DC fuse required for DC input voltage |
External fuse (recommended) | 3 x circuit breakers 6 A, 10 A, 16 A, characteristic: B or C or motor circuit breakers, setpoint: 2.5 A, setting range: 2.5 … 4 A |
Insulation voltage (PRI-SEC) | DC 4.242 kV |
Isolation voltage (PRI-GND) | DC 2.2 kV |
Insulation voltage (SEC-GND) | DC 0.7 kV |
Protection class | I |
Protection class | IP20 (per EN 60529) |
Feedback voltage | ≤ DC 35 V |
Overvoltage category | II |
Transient protection, primary | Varistor |
Short circuit protection | Yes |
No-load proof | Yes |
Parallel operation | Yes |
Series connection | Yes |
MTBF | > 500,000 h (per IEC 61709) |
Connection type (1) | Input |
Connection technology | CAGE CLAMP® |
WAGO terminal | WAGO 231 Series |
Solid conductor | 0.08 … 2.5 mm² / 28 … 12 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 12 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inch |
Connection type (2) | Output |
Connection technology 2 | Push-in CAGE CLAMP® |
WAGO terminal 2 | WAGO 831 Series |
Solid conductor (2) | 0.5 … 10 mm² / 20 … 8 AWG |
Fine-stranded conductor (2) | 0.5 … 10 mm² / 20 … 8 AWG |
Strip length (2) | 13 … 15 mm / 0.51 … 0.59 inch |
Connection type (3) | Signaling |
Connection technology 3 | CAGE CLAMP® |
WAGO terminal 3 | WAGO 733 Series |
Solid conductor (3) | 0.08 … 0.5 mm² / 28 … 20 AWG |
Fine-stranded conductor (3) | 0.08 … 0.5 mm² / 28 … 20 AWG |
Strip length (3) | 5 … 6 mm / 0.2 … 0.24 inch |
Width | 77 mm / 3.031 inch |
Height | 171 mm / 6.732 inch |
Length from upper-edge of DIN-35 rail | 179 mm / 7.047 inch |
Note on dimensions | Height including pluggable connector |
Type of mounting | DIN-35 rail (EN 60715) in 2 positions |
Weight | 1300 g |
Surrounding air (operating) temperature | -25 … 70 °C (Device start at -40 °C type-tested) |
Surrounding air (storage) temperature | -25 … 85 °C |
Relative humidity | 5 … 96 % (no condensation permissible) |
Derating | -3 %/K (> 50 °C) |
Pollution degree | 2 |
Climatic category | 3K3 (per EN 60721) |
Conformity marking | CE |
Standards/specifications | EN 60950; EN 61204-3; EN 61558-2-16; UL 60950; UL 508 |
Product Group | 6 (Interface Electronics) |
Country of origin | DE |
GTIN | 4045454909901 |